5�6�3�- POWER CUT
Note: This menu is displayed if the wire cover sensor has been activated.
L1
CortE
Figure 132:Power cut
The general relay of the Dispenser can be disconnected in this menu. To do so, long press the
button.
The unit opens the general relay and displays the screen shown in Figure 133 permanently.
L1
rEArME
CortE
Figure 133:Closing Process Complete Screen�
Long press the button to rearm the general relay.
5.7.- RS-485 COMMUNICATIONS
The Dispensers feature an RS-485 communications port.
The unit has the following communications system installed by default: MODBUS RTU ® .
5�7�1�- CONNECTIONS
The RS-485 cable must be wired with twisted pair cable with mesh shield, with a maximum
distance between the Dispenser and the master unit of 1200 metres.
Up to 32 Dispensers can be connected to this bus.
Use an intelligent RS-232 to RS-485 network protocol converter to establish the
communications with the master unit.
114
Dispenser Universal System
Instruction Manual