5�6�2 PROGRAMMING THE AUXILIARY RELAY, AUX
Open the auxiliary output screen and hold down the RESET key for 2 seconds to program the
operation of the auxiliary relay.
RESET
Prealarm (ALAR)
This is activated when > 0.5•IΔn, in 200 milliseconds.
Fault relay (AUXF)
Shows fault events in the unit, such as undervoltages or faults in the
external sensor.
Operates in the positive safety status.
17
Instruction Manual
RGU-2 Earth Leakage Relay