3 TECHNICAL CHARACTERISTICS
3.1 Measuring instrument
Supply circuit
(connector B : cables brown and green)
AC voltage
100…400 Vac
DC voltage
70…315 Vdc
Frequency
50 / 60 Hz
Consumption
9 VA
Safety / Insulation
Category III 300 Vac (acc. to EN 61010)
Measurement circuit (FS means full scale)
Voltage range
10…400 Vac. (Phase - Neutral)
17…690 Vac (Phase - Phase)
Current range (…/2V)
2,5% …100% of clamp FS
Frequency
45…65 Hz
Accuracy (Only CIR-e
3
. See current clamps error in the clamps characteristics)
Voltage
0,5 %
Current
0,5 %
Power
1 %
Energy
1 %
Battery
Battery (eq. manufactured before 2012)
NiMH
Battery (eq. manufactured after 2012)
BR2032
Equipment manufactured before 2012 have a rechargeable battery
Equipment manufactured after 2012 have non rechargeable battery type BR2032.
CIRCUTOR recommends the battery replacement every 5 years.