5�22�-VOLTAGETHDALARM
InthispointthethresholdsabovewhichtheVoltage
THDalarm(E08)isactivatedcanbeconfigured�
Thealarmmustbeenabled(
5�19�- ENABLING
ALARMS”
Theprogrammedvaluesareusefulforthe3
phaseswhichtheunitmeasures�
Pressthe
keytoentereditingmode�Itis
identifiedbythe
symbolandtheblinkingof
thedigitstobemodified�
Theparameterstobeconfiguredare:
TheLo value : whentheunitexceedsthisvaluefor30minutes,alarmE08 is
triggered,andifalarmE11isenabled,theSMART III FASTunitentersNo Connection
statusandactivates alarmE11
TheHI value: iftheunitexceedsthisvaluefor30seconds,alarmE08istriggered,
andifalarmE12isenabled,theSMART III FASTunitentersDisconnection statusand
activates alarmE12
IftheunitfallsbackundertheLo valuefor10minutes,itdeactivatesthealarmsandreturns
tothenormaloperatingstatus�
IntheNo Connectionstatus,theunitdoesnotconnectthestages,butalsodoesnot
disconnectthemiftheoperationrequiresit�
IntheDisconnectionstatus,itdisconnectsthestagesanddoesnotallowthemtoconnect�
The keyincreasesthedigitvalue�
The keydecreasesthedigitvalue�
The keyskipstothepreviousdigit�
The keyskipstothenextdigit�
Press tovalidatethedata;the symboldisappearsfromthedisplay
Lo Valueand HI Value:
Maximum value: 99%
Minimum value: 1%