Circutor MDC-4 Manuel d'utilisateur Page 21

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 30
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 20
Press key to access the next programming step.
4�8�6� Deleting the energy value
CleaEnergy
NO
In this step you select whether or not to delete
the energy value.
Press the
button to select between the two
possible options: No or Yes.
Press key to access the next programming step.
4�8�7� Deleting the output relay disconnection times�
Clea
out % Time
NO
In this step you select whether or not to delete
the % of time that each output relay has been
disconnected.
Press the button to select between the two
possible options: No or Yes.
Press key to access the next programming step.
4�8�8� Level of output relay no� 1
out1 Level (%)
75
In this step you program the value (%) of con-
tracted power from which the output relay is
disconnected.
Example: If OUT1 is programmed to 75%, when the maximum demand value reaches 75%
of the contracted power in the installation, output relay no.1 will be disconnected, thus discon-
necting all the corresponding loads.
Press the key to increase the digit that is currently ashing.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the remaining values.
Maximum value: 99%.
Minimum value: 0 %.
Default: OUT1 : 75% , OUT2 : 80%, OUT3 : 90%, OUT4 : 95%
Press key to access the next programming step.
4�8�9� Hysteresis of output relay no� 1
out1 Hyst (%)
05
The hysteresis value, i.e., difference between the
relay connection and disconnection point, in %,
is programmed in this step.
Press the
button to increase the digit that is
currently ashing.
21
Instruction Manual
MDC-4
Vue de la page 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 29 30

Commentaires sur ces manuels

Pas de commentaire