Circutor AR6 Series Manuel d'utilisateur Page 15

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 69
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 14
AR6 portable network analyzer
User Manual Page 15 of 69
Permanent overvoltage
1,000 V
RMS
Transitory overvoltage <1 s
2,500 Vpeak
Absolute maximum voltage
6 kV
Consumption
0.04 VA
Maximum voltage in the voltage measurement circuit
1000 V CAT III / 600 V CAT IV for elevations below 2000 m.
1000 V CAT II / 600 V CAT III / 300 V CAT IV for above 2000 m
4.7 UNIT ACCURACY
Variable
Resolution
Accuracy
Margin
Currents * (2 V input)
0.1 mA
± 0.5%
10% … 120% of In
Voltage
0.01 V
± 0.5%
20% … 120% of Un
Active power
0.1 W
± 1%
Reactive power
0.1 VAr
± 1%
Apparent power
0.1 VA
± 1%
Frequency
0.01 Hz
± 0.01 Hz
45 … 65 Hz
Active Energy
1 W·h
± 1%
Reactive energy
1 VAr·h
± 1%
Voltage THD
% x 10
± 0.5%
10% … 120% of Un
Current THD
% x 10
± 0.5%
20% … 120% of In
PST Flicker
% x 10
± 5%
Voltage Imbalance
% x 10
Voltage Asymmetry
% x 10
Crest Factor
x100
± 0.5%
1.0…1.875
* The unit's accuracy in current and in power does not include the margins of error of the
clamps connected to it.
4.8 ENVIRONMENTAL CONDITIONS
Operating temperature
-10…+50 ºC
Storage temperature
-10…+60 ºC
Altitude
2,000 m
Humidity without condensation
5...95%
Vue de la page 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 68 69

Commentaires sur ces manuels

Pas de commentaire