Circutor AR6 Series Manuel d'utilisateur Page 40

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 69
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 39
AR6 portable network analyzer
Page 40 of 69 User Manual
11.4.1 Events grouping in accordance with UNIPEDE criteria
- In three-phase systems a swell starts when the value U
RMS
of the voltage of one or more
phases exceeds the set-point for detecting an over-voltage (usually 110% of rated value); it
ends when the value U
RMS
for all the phases is less than or equal to the set-point minus the
configured hysteresis value (t0)
Fig.11-9.- Start and end of a swell in a three-phase system
- In three-phase systems a sag starts when the value U
RMS
of the voltage of one or more
phases is below the threshold for detecting sags (usually 90% of rated value); it ends when
the U
RMS
is greater than or equal to the threshold plus the configured hysteresis value (t1)
or if all phases are below the interruption level (usually 10% of rated value).
Fig.11-10.- Start and end of a sag in a three-phase system
- In three-phase systems an interruption starts when the value U
RMS
of the voltage of all the
phases is below the threshold for detecting interruptions (usually 10% of rated value); it
ends when the value URMS of any phase is greater than or equal to the threshold plus the
configured hysteresis value (t2).
Fig.11-11.- Start and end of an interruption in a three-phase system
In the values shown for the individual phases, the time shown refers to each event; no
grouping is done.
The available dynamic menu options for the UNIPEDE table screen are:
Vue de la page 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 68 69

Commentaires sur ces manuels

Pas de commentaire