Circutor CDP-0 Manuel d'utilisateur Page 30

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 74
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 29
CDP
30 Instruction Manual
Figure 27: Single-phase installation with 3 loads to connect (Load 1 Connected).
In this situation the CDP-G maintains the system without adding or removing any
loads for a time equalling the longer of the configured “Reconnection time” and
Min. disconnection time” variables, in order to achieve system stability (in this
case 5 minutes).
To check if this load must be disconnected, the CDP-G waits for the amount of
time programmed in the “Min. connection time” variable and then checks if the
following condition is met:
Disconnection condition:

 
< .  
(

= 0%) 0% ≤ 50%
this condition is met relay 1 stays connected
Then, the CDP-G will check whether it can connect the next load. To do so, it
must verify whether the 2 connection conditions are met:
Condition 1:

 
100 .  
(


100 = 60%) 60% ≤ 90% this condition is met
Loads
Vue de la page 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 73 74

Commentaires sur ces manuels

Pas de commentaire