CDP
Instruction Manual 31
Condition 2:
-If Injection Margin = 0% It checks whether:
Pgrid < 2 x (0.03) x Pconsumed
-If Injection Margin ≠ 0% It checks whether:
Pgrid < 2 x Injection Margin x Pconsumed
0 < 2 x 0.03 x 6000 this condition is met
If the 2 conditions are met, the relay closes and connects the load.
So, the CDP-G will connect the second load, as shown in Figure 28:
Figure 28: Single-phase installation with 3 loads to connect (Load 1 and 2 Connected).
In this situation the CDP-G maintains the system without adding or removing any
loads for the amount of time configured in the “Reconnection time” variable, in
order to achieve system stability (in this case 5 minutes).
To check if this load must be disconnected, the CDP-G waits for the amount of
time programmed in the “Min. connection time” variable and then checks if the
following condition is met:
Loads