Circutor computer SMART Series (Available until stock) Manuel d'utilisateur Page 24

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 33
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 23
M98235701-03-12A
Computer Smart 6/Computer Smart 12
- 23 -
When the 440 V capacitor power reference is used for a 400 V grid voltage, the following table is used:
CT Ratio
(I
p
/I
s
)
Power in kvar of the smallest stage, in kvar, at 440 V
2.5 5.00 7.5 10.0 12.5 15.0 20.0 25.0 30.0 40.0 50.0 60.0 75.0 80.0
150/5 0.09
0.18
0.27
0.36
0.45
0.54
0.72
0.90
200/5 0.07
0.14
0.20
0.27
0.34
0.41
0.54
0.68
0.81
250/5 0.05
0.11
0.16
0.22
0.27
0.33
0.43
0.54
0.65
0.87
300/5 0.05
0.09
0.14
0.18
0.23
0.27
0.36
0.45
0.54
0.72
0.90
400/5
0.07
0.10
0.14
0.17
0.20
0.27
0.34
0.41
0.54
0.68
0.81
500/5
0.05
0.08
0.11
0.14
0.16
0.22
0.27
0.33
0.43
0.54
0.65
0.81
0.87
600/5
0.05
0.07
0.09
0.11
0.14
0.18
0.23
0.27
0.36
0.45
0.54
0.68
0.72
800/5 0.05
0.07
0.08
0.10
0.14
0.17
0.20
0.27
0.34
0.41
0.51
0.54
1000/5 0.04
0.05
0.07
0.08
0.11
0.14
0.16
0.22
0.27
0.33
0.41
0.43
1500/5 0.04
0.05
0.05
0.07
0.09
0.11
0.14
0.18
0.22
0.27
0.29
2000/5 0.04
0.05
0.07
0.08
0.11
0.14
0.16
0.20
0.22
2500/5 0.04
0.05
0.07
0.09
0.11
0.13
0.16
0.17
3000/5 0.04
0.05
0.05
0.07
0.09
0.11
0.14
0.
14
4000/5 0.04
0.05
0.07
0.08
0.10
0.11
IMPORTANT!:
When the C/K adjustment is configured under the real values, there will be a series of continuous
connections and disconnections with minor load variations. (The system performs more operations than
those actually needed).
When the C/K adjustment is configured as "high" (10%), the regulator will need a higher reactive power
demand to perform the switching operations and, therefore, perform fewer operations.
Calculation of the C/K Factor
In the case of values that have not been included in the table, the C/K factor can be calculated as follows:
The reactive power of the smallest capacitor Q and the grid voltage U must be known. The current of this
capacitor will be then calculated as
V.
Q
C
I
3
=
The transformation ratio of the current transformer must also be known. This is the K factor:
sec
I
prim
IK /=
where: Iprim is the nominal current of the transformer's primary (for example, it would be 250A in a 250/5)
Isec is the transformer's secondary current. Usually 5 A.
Therefore, the C/K factor will be:
VK
Q
K
I
KC
C
==
3
/
For example: In a 400V unit, the smallest capacitor is 60 kVAr with a current transformer with a 500/5 ratio.
The calculation is as follows:
K factor
1005/500
=
=
K
Current of the smallest capacitor
AI
C
6,86
4003
100060
=
=
C/K value
866,0
100
6,86
/ ===
K
Ic
KC
When the 60kvar power is referenced to 440 V, it must be multiplied by Ugrid^2/440^2, so that the previous
example would be:
AI
C
6.71
2^4403
400*100060
=
=
72,0/
=
KC
Vue de la page 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 32 33

Commentaires sur ces manuels

Pas de commentaire