If the value entered is greater than the maximum programming value, the digits ash for 2
seconds and the programmed value is deleted.
Maximum programming value: 9.999.
Minimum programming value: 0.
4�6�10� Maximum demand variable
On this screen the variables to integrate into the Maximum
Demand concept are selected.
The display shows the digits that identify that code for the
variable to be integrated according to Table 10
Table 10: Codes for maximum demand variables
Parameter Code
Active three-phase power 16
Apparent three-phase power 34
Three-phase current 36
None 00
The key jumps between the different options.
To validate the information and go to the next programming step, press .
4�6�11� Period of maximum demand integration
On this screen the maximum demand integration period is
programmed.
To enter or modify the integration period value, press the
key
repeatedly, increasing the value of the ashing digit.
When the on-screen value is that desired, press the
key to
go to the next digit to modify the other values.
If you press the key after changing the last digit, it will jump back to the rst digit so you
can modify the previously programmed values again.
The integration period may range from 1 to 60 minutes.
To validate the information and go to the next programming step, press .
If the value entered is greater than the maximum programming value, the digits ash for 2
seconds and the programmed value is deleted.
29
Instruction Manual
CVM-C5
Commentaires sur ces manuels