LEd1
LEd2
LEd3
LEd4
Support of alarm signalling. In
the situation when the support
function is switched on , after
the alarm state retreat, the
signalling diode is not blanked
. It signals the alarm state till its
blanking moment by means of
the push-but-
ton combination. This function
concerns only and exclusively
the alarm signaling, thus relay
contacts will operate without
support according to the chosen
type of alarm.
oFF – function switched off
on – function switched on
out
Parameter
symbol
Description Range of changes
P_An
Input quantity, on which the
analog output has to react..
InP – main input (indicated
value).
HoUr – Real Time Clock
AnL
Lower threshold of the analog
output. One must give the value,
for which we want to obtain the
minimal value of signal on the
analog output.
-19999...99999
AnH
Upper threshold of the analog
output. One must give the value
on which we want to obtain the
maximal value of signal on the
analog output( 10 V or 20 mA).
-19999...99999
tYPA
Analog output type.
0_10U – napięciowe 0..10V
0_20A – prądowe 0..20mA
4_20A – prądowe 4..20mA
Table 5