Circutor DHB Series Manuel d'utilisateur Page 31

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 50
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 30
31
6.4 Register map
The register map of the DHB-424 meter is presented below
Notice:
All given addresses are physical addresses. In some computer pro-
grams logic addressing is applied, then addresses must be increased
of 1.
Table 8
Range
of address
Value type Description
4000-4049 integer (16 bits) Value placed in a 16-bit register.
7000-7039 float (32 bits)
Value placed in two successive 16-
bit registers. Registers include the
same data as 32-bit register from
the area 7500. Registers are only for
readout.
7200-7326 float (32 bits)
Value placed in two successive 16-
bit registers. Registers include the
same data as 32-bit register from
the area 7600. Registers can be
read out and written.
7500-7519 float (32 bits)
Value placed in a 32-bit register.
Registers are only for readout.
7600-7663 float (32 bits)
Value placed in a 32-bit register.
Registers can be read out and
written.