8. TECHNICAL DATA
Measuring ranges
Table 13
Kind of input Indication range Class
Pt100
-205...855°C (-200...850°C)
0.1
Pt500
Pt1000
400 W 0...410 W (0...400 W)
4000 W 0...4010 W (0...4000 W)
Thermocouple of J type -200...1200 °C (-100...1200 °C)
Thermocouple of K type -200...1370 °C (-100...1370 °C)
Thermocouple of N type -200...1300 °C (-100...1300 °C)
Thermocouple of E type -200...1000 °C (-100...1000 °C)
Thermocouple of R type -50...1768 °C (-50...1760 °C)
Thermocouple of S type -50...1768 °C (-50...1760 °C)
Voltage input 0...10 V -13...13 V (-10...10 V)
Current imput -24...24 mA (-20...20 mA)
Voltage input 60 mV -10...63 mV (0...60 mV)
Current time 00.00...23.59 0.5 sec/24 h
Additional error:
- of automatic thermocouple cold junction temperature compensation:
1 °C
- of automatic wire resistance compensation for thermoresistors:
0,5 °C
- of automatic wire resistance compensation for resistance measurement:
0,2 W
- of temperature changes: for analog outputs 50 % of the class / 10 K
for analog inputs 100 % of the class / 10 K
Inputs parameters:
- resistance of the supply input [V]: > 1 M W
- resistance of the current input [mA]: 12 ±1 W%
- current flowing through the resistance thermometer 270 ± 10 uA
- resistance of wires connecting the resistance thermometer with transmitter: <10 W