Page 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL(M010B01-03-15B)Power analyzerCVM-B100 CVM-B150

Page 2

3.- UNIT INSTALLATION 3.1.- PRIOR RECOMMENDATIONSIn order to use the unit safely, it is critical that individuals who handle it follow the safety

Page 3

5.1.7.- Integrated functions.On this screen, Figure 84, you can view the status of the digital inputs integrated in the unit.Figure 84: Display scre

Page 4 - CONTENTS

5.1.8.- Expansion modules.NB: This option only appears when the unit is connected to an expansion module of Transistor Digital Inputs/Outputs (M-CV

Page 5

Figure 86: Display screen of digital inputs of an expansion module.The following options appear in the lower area: Previous, moves up the list of al

Page 6

5.2.- ALARM MENU The screen in Figure 87 is the alarm display menu screen. Where all the alarms programmed in the unit and in the connected exp

Page 7 - REVISION LOG

Figure 88: Alarm menu description table.The programmed alarms description table , Figure 88, is made up of 4 columns:Cd. : Indicates the code of the v

Page 8

5.3.- ENERGY CLOSES MENU The screen in Figure 89 is the home screen for the energy close menu.Figure 89: Main screen of the energy closes menu.

Page 9

5.3.1.- Active energy closes III of the total tariff and of reactive energy III of the total tariff.This screen displays the graphical represent

Page 10 - Instruction Manual

When a given close is selected the display shows: The value of the selected energy close.The difference, in %, between the most recent energy close wi

Page 11

5.4.1.- Alarm logThis screen shows the log of the last 50 alarms occurring in the unit and installed expansion modules, including a brief descript

Page 12 - 3.3.- UNIT TERMINALS

Example: Alarm M0_S3 act with latch M0, Indicates the module where the alarm was activated: M0, is an alarm triggered in t

Page 13

3.2.- INSTALLATIONThe unit is installed on a panel. All connections are located inside the electric panel.Table 2: Panel drill holes for installation.

Page 14 - POWER SUPPLY

Next, scrolls down the event log.. Back, returns to the main screen of the log menu, Figure 91. Main menu, back to the main menu, Figure 25.Use t

Page 15

Use the keys and to browse the various menus.To access the selected menu press the key .If no key is pressed for 5 minutes, the display screen cha

Page 16 - Measurement system:

5.5.2.- Integrated functions.On the integrated functions screen, Figure 97, you will view the configuration of the communications and digital i

Page 17

5.5.3.- Expansion modules.On the expansion modules screen, Figure 98, you will view the model, serial number and rmware version of each of the exp

Page 18

5.5.3.1.- Expansion modules of Transistor and Relay digital inputs/outputsThe screen in Figure 99, is one of the information display screens for the e

Page 19

Figure 100: Digital outputs information screen (Transistor Digital Inputs/Outputs Module)If no key is pressed for 5 minutes, the display screen change

Page 20

Back, returns to the expansion modules information screen, Figure 98. Main Menu, back to the main menu, Figure 25.Use the keys and to select th

Page 21

5.5.3.3.- Modbus TCP (Bridge) communications expansion modulesThe screen in Figure 103, is a screen that displays the information of the Modbus TCP co

Page 22 - Figure 12) until the

Figure 104: Information screen of the Modbus/TCP ( Bridge) module (RS-485 Gateway).5.5.3.4.- LonWorks communications expansion modulesThe screen in Fi

Page 23 - Figure 14)

5.5.3.5.- Probus communications expansion modulesThe screen in Figure 106 display screen, is a screen that displays the information of the Probus co

Page 24

3.3.- UNIT TERMINALSThe CVM-B terminals are distributed between the upper and lower face of the unit.3.3.1.- Terminals on the upper face Table 3:List

Page 25 - Figure 17

5.5.3.6.- MBus communications expansion modulesThe screen in Figure 107 display screen, is a screen that displays the information of the MBus communic

Page 26

5.5.3.7.- Datalogger expansion modulesThe screen in Figure 108 display screen, is a screen that displays the information of the Datalogger communicati

Page 27 - 4.2.- MEASUREMENT PARAMETERS

Figure 109: Datalogger (Port) module information screen.122CVM-B100 - CVM-B150Instruction Manual

Page 28 - Table 6: Function of keys

5.5.4.- CIRCUTOR S.A.This screen, Figure 110, shows all the Circutor contact information.Figure 110: Circutor screen.The following options appear i

Page 29 - Figure 19):

5.6.- SETUP MENU If the setup menu is protected by an access password there is an icon on the main menu screen, see Figure 111.Figure 111:Protected

Page 30

Previous, selects the previous digit. Next, selects the next digit. Conrm, to conrm the access password programmed and enter the home screen

Page 31 - Figure 22, which shows the

5.6.1.- Date and time.The current date and time are selected on this screen, Figure 114.Figure 114: Date and time conguration screen.The digit sel

Page 32

5.6.2.- Time zone.The time zone is selected on this screen Figure 115.Figure 115: Time zone conguration screen.The following options appear in th

Page 33

If no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage measurement of 4 parame

Page 34

5.6.4.- Access key.The access key to the unit setup menu is selected on this screen Figure 117.Figure 117: Access key conguration screen.The digit

Page 35

3.3.2.- Terminals on the lower faceTable 4:List of terminals on the lower face of the CVM-B.Unit terminals20 : Auxiliary power supply. 25: S2, Current

Page 36 - Figure 25:Main screen

5.6.5.- Measurement connection mode.This screen, Figure 118, is for selecting the measurement connection mode.Figure 118: Measurement connection mo

Page 37

5.6.6.- Ratio of voltage transformers.The voltage transformer ratio is selected on this screen, Figure 119. The following is programmed:  The val

Page 38

If no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage measurement of 4 parame

Page 39 - Figure 27

5.6.7.- Ratio of current transformers.The current transformer ratio is selected on this screen, Figure 120. The following is programmed:  The val

Page 40

Calculated current, to select a software-based calculation by the unit of the neutral current. ● For all parameters: Previous, selects the prev

Page 41

5.6.8.- Display of variables.The parameters to be displayed for each type of instantaneous, incremental and demand value are selected on this scree

Page 42 - Figure 31):

5.6.9.- Demand.The maximum demand conguration parameters are selected on this screen Figure 122:  The type of integration of the demand.  The

Page 43

Main Menu, back to the main menu, Figure 25.Use the keys and to select the different options.To conrm the selection, press the key .In

Page 44 - Figure 31

● When programming the number of quadrants: Consumption, installation that works with 2 quadrants. Consumption and generation, installation tha

Page 45

The parameter selected is indicated in white.The following options appear in the lower area: ● When programming the cost of the tariffs: , ...

Page 46

3.4.- CONNECTION DIAGRAMS3.4.1.- Three-phase network measurement with a 4-wire connection.Measurement system:Secondary winding of the current transf

Page 47

5.6.12.- Energy generation costs.The energy generation costs are selected on this screen Figure 125:  The cost per kWh of electricity of tariff 1

Page 48 - Figure 36

Next, selects the next parameter. Conrm, conrms and saves in the memory the values programmed on the screen. Back, returns to the home scre

Page 49 - Figure 38

The parameter selected is indicated in white.The following options appear in the lower area: , ... The ten possible digits to program. Comma.

Page 50

5.6.14.- CO2 generation emissions.The carbon generation emission ratios are selected on this screen Figure 127.The carbon emissions ratio is the am

Page 51

Use the keys and to select the different options.To conrm the selection, press the key .CO2 generation emissions ratio: Maximum value: 100.000

Page 52 - Figure 40

After selecting the output to congure, Figure 129, the following parameters can be congured:  The variable code that controls the relay.  The Pr

Page 53 - Figure 42

NB: To cancel the operation of a digital output, the 0 code must be programmed.If no key is pressed for 5 minutes, the display screen changes automati

Page 54 - Figure 43

Table 21 ( Continuation ): Code of variables for programming the digital outputs and transistor.VariableL1 L2 L3 IIITotal Reactive Energy Generated (4

Page 55

(1) The integrated variables are those that the unit has as standard.(2) If in the unit there is more than one module connected with the same type of

Page 56

Conrm, conrms and saves in the memory the values programmed on the screen. Back, returns to the home screen of the setup menu Figure 113. Ma

Page 57

Measurement system:Secondary winding of the current transformer: (MC3 type transformer)Secondary winding of the neutral current transformer: PowerS

Page 58

Table 22(Continuation):Units and maximum and minimum values of the programming variables of the digital outputs.Variable Units Maximum MinimumActive P

Page 59

● When programming the disconnection delay (OFF) of the relay digital output:The disconnection delay is programmed in seconds. , ... The ten pos

Page 60

● When programming the latch:The latch is selected in this parameter, i.e., if the relay digital output is locked after it has been tripped, even whe

Page 61 - screen

Output 1, to select the conguration of the digital output of transistor 1. Output 2, to select the conguration of the digital output of trans

Page 62

The parameter selected is indicated in white.The following options appear in the lower area:● When programming the variable code which controls the t

Page 63

● When programming the minimum value below which the transistor is activated:The units and maximum and minimum values of the variables to program are

Page 64 - Figure 50

If no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage measurement of 4 parame

Page 65

Disconnection delay (OFF): Maximum value: 999s. Minimum value: 0s.If no key is pressed for 5 minutes, the display screen changes automatically to th

Page 66

5.6.16.2.- Impulse mode of transistor digital outputWhen selecting the impulse mode, Figure 132, the conguration parameters are:  The variable

Page 67

● When programming the variable code which controls the transistor digital output (Table 21): , ... The ten possible digits to program. Delete

Page 68 - Figure 53

3.4.2.- Three-phase network measurement with a 3-wire connection. Measurement system:Secondary winding of the current transformer: (MC1 type tra

Page 69

● When programming the low period:The low period is the time that the pulse is at its minimum value.The programmed value is a multiple of 10 ms, i.e.

Page 70

To conrm the selection, press the key .High period: Maximum value: 65536. Minimum value: 1.If no key is pressed for 5 minutes, the display screen

Page 71 - Figure 56

5.6.17.1.- Conguration of digital inputs, Tariff mode.When selecting the tariff mode the two inputs operate in the same mode; they cannot be programm

Page 72 - Figure 58

5.6.17.2.- Conguration of digital inputs, impulse mode.After selecting the conguration of an input in impulse mode, you must select the input t

Page 73

Next, selects the next parameter. Conrm, conrms and saves in the memory the values programmed on the screen. Back, returns to the main con

Page 74 - Figure 60):

Conrm, conrms and saves in the memory the values programmed on the screen. Back, returns to the main conguration screen for digital inputs Fi

Page 75

5.6.17.3.- Conguration of digital inputs, logic state mode.After selecting the conguration of an input in logic mode, you must select the input

Page 76 - Figure 60

5.6.18.- Integrated communications.Select the RS-485 communications protocol and conguration parameters on the integrated communications congurat

Page 77

The parameter selected is indicated in white.The following options appear in the lower area:● When programming the Np:The Np is the peripheral number

Page 78

If no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage measurement of 4 parame

Page 79

Measurement system: Secondary winding of the current transformer: (MC3 type transformer)PowerSupplyVL1 VL2VL3L1L2L3POWER SUPPLYN VL3 L2VL1VVL1 VL2 V

Page 80 - Figure 65

5.6.18.2.- Conguration parameters, BACnet protocol.When selecting the BACnet communications protocol, Figure 138, you can program the following p

Page 81

If no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage measurement of 4 parame

Page 82

If no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage measurement of 4 parame

Page 83

If no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage measurement of 4 parame

Page 84 - Figure 68

Minimum value: 1 minuteIf no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage

Page 85

Format dd/mm/yyyy. Previous, selects the previous parameter. Next, selects the next parameter. Confirm, confirms and saves in the memo

Page 86

6.- INTEGRATED COMMUNICATIONSThe CVM-B units have one RS-485 communications port. The unit has as standard two communications protocols: MODBUS RTU ®

Page 87

6.2.- MODBUS PROTOCOLThe MODBUS protocol is a communication standard in the industry that enables the network connection of multiple units, whe

Page 88 - Figure 71

6.2.1.- Example of MODBUS queryQuery: Instantaneous value of the L1 phase voltageAddress FunctionInitial reg-isterNo. of regis-tersCRC0A 04 0000 0002

Page 89 - Figure 71

Table 24: Modbus memory map: measurement variablesParameter Symbol Instantaneous Maximum MinimumUnits (1)Phase voltage L1 V1 00-01 100-103 300-303 157

Page 90

3.4.3.- Three-phase network measurement with a 3-wire connection and transformers with an ARON connection. Measurement system: Secondary winding of th

Page 91

Table 24 ( Continuation) : Modbus memory map: measurement variablesParameter Symbol Instantaneous Maximum MinimumUnits (1)Current THD % In THDIN 5C-5D

Page 92

Table 25 ( Continuation ) : Modbus memory map: current energy variables.Parameter SymbolAddress1 (1)2 (1)Apparent energy consumed L1 kVAh L1 544-545 5

Page 93 - Figure 75

Table 25 ( Continuation ) : Modbus memory map: current energy variables.Parameter SymbolAddress1 (1)2 (1)Active energy generated L1 kWh L1 (-) 5C8-5C9

Page 94

Table 25 ( Continuation ) : Modbus memory map: current energy variables.Parameter SymbolAddress1 (1)2 (1)Inductive reactive energy generated L1 kvarhL

Page 95

Table 25 ( Continuation ) : Modbus memory map: current energy variables.Parameter SymbolAddress1 (1)2 (1)Capacitive reactive energy generated L1 kvarh

Page 96 - Figure 80)

6.3.4.- Voltage and current harmonics.The rst two registers are the RMS value of the fundamental harmonic, followed by the 50 harmonics, each one of

Page 97 - Figure 81)

Table 27 ( Continuation ) : Modbus memory map: Voltage and current harmonics.Parameter Voltage L1 Voltage L2 Voltage L3 Neutral VoltageUnits (1)41st O

Page 98 - Table 20:Harmonics

Table 27 ( Continuation ) : Modbus memory map: Voltage and current harmonics.Parameter Voltage L1 Voltage L2 Voltage L3 Neutral VoltageUnits (1)36th O

Page 99

6.3.7.- Unit conguration variablesThe following functions are implemented for these variables: Function 0x04: reading registers. Function 0x10: Writi

Page 100 - Figure 25

Table 32: Conguration of local timeLocal time parameterLocal time Value Local time ValueUTC+1 0x0000 UTC-11 0x000CUTC+2 0x0001 UTC-10 0x000DUTC+3 0x

Page 101 - Figure 86, where you

3.4.4.- Two-phase network measurement with a 3-wire connection.Measurement system:Secondary winding of the current transformer: (MC1 type transf

Page 102 - Figure 85

6.3.7.5.- Measurement connection modeThis parameter occupies 1 register.Table 35: Modbus memory map: Conguration variables (Measurement connection mo

Page 103

6.3.7.7.- Display of variablesThis parameter occupies 1 register.Table 37:Modbus memory map: Conguration variables (Display of variables).Selection o

Page 104 - Table 21

6.3.7.9.- Installation dataThese parameters occupy 1 register each.Table 40: Modbus memory map: Conguration variables (Installation data)Installation

Page 105

6.3.7.12.- Relay digital outputsThe Maximum Value and Minimum Value conguration variables occupy 2 registers each.All other variables occupy 1 regi

Page 106 - Figure 89

Table 44 ( Continuation): Units and maximum and minimum values of the programming variables of the digital outputs.Variable Units Maximum MinimumMaxim

Page 107

6.3.7.14.- Digital inputsThe Input Name conguration variable occupies 4 registers.The Units conguration variable occupies 3 registers.All other vari

Page 108 - Figure 93, has 4 columns:

6.3.7.16.- User interfaceThese parameters occupy 1 register each.Table 48:Modbus memory map: Conguration variables (user interface)User interfaceConf

Page 109

Example: Query: Reading the position of input channels.AddressFunc-tionInitial reg-isterNo. of regis-tersCRC0A 04 2850 0001 XXXX Address: 0A, Periphe

Page 110

Table 52 (Continuation): Modbus memory map: Configuration variables (Configuration of the parameter customisation screens)Conguration of the paramete

Page 111 - Figure 95

Table 54: Modbus memory map: Conguration variables (Conguration of the parameter customisation screens)Conguration of the parameter customisation s

Page 112

2CVM-B100 - CVM-B150Instruction Manual

Page 113

3.4.5.- Single-phase network measurement, phase to phase, with a 2-wire connection.Measurement system: Secondary winding of the current transformer:

Page 114

Table 55 ( Continuation) : Configuration of custom screens: Variables.Variables parameterVariable Value Variable ValueApparent Power 0x000ACO2 Emis

Page 115

6.3.8.- Other unit variables6.3.8.1.- Firmware versionThese parameters occupy 6 registers.Table 59: Modbus memory map: Firmware version.Firmware versi

Page 116 - Figure 102, with

6.3.8.5.- Alarm status6.3.8.5.1.- Relay digital outputsThe Latch variable occupies 2 registers.All other variables occupy 1 register each.Table 63: Mo

Page 117

6.3.8.5.2.- Transistor digital outputsThe Latch variable occupies 2 registers.All other variables occupy 1 register each.Table 64: Modbus memory map:

Page 118

6.3.8.6. Energy closesThe Energy variables occupy 90 registers.All other variables occupy 1 register each.Energy closesVariable(1) Address 1 day activ

Page 119

Table 65 ( Continuation ) : Modbus memory map: Deleting parametersDeleting parameters Address Value to be sentDeleting the alarm logs 0840 0x00FFDelet

Page 120

6.5.- PICS MAPPICSVendor Name: CIRCUTORProduct Name: CVM-B100 | CVM-B150Product Model Number: 0823Application Software

Page 121

DESCRIPTION SYMBOL ID OBJECTS OBJECT NAME UNITSPotencia reactiva Reactive power kvar 2 AI8 ReactPwrPh2 kvarFactor de potencia Power factor PF 2 AI9 Pw

Page 122

DESCRIPTION SYMBOL ID OBJECTS OBJECT NAME UNITSPotencia aparente trifásicaThree phase aparent powerkVAIII AI43 AppPw3Ph kVAMáxima demanda I1 Maximum d

Page 123

7.- EXPANSION MODULESThe unit has following expansion modules that can be connected to it.The modules are:  Transistor Digital Inputs/Outputs (M-CV

Page 124 - Figure 111

3.4.6.- Single-phase network measurement, phase to neutral, with a 2-wire connection.Measurement system: Secondary winding of the current transformer:

Page 125

A.- Protective cove version 1To install, rstly remove the protective cover of the expansion connector located at the rear of the unit, Figure 142.

Page 126

B- Protective cove version 2To install, rstly remove the protective cover of the expansion connector located at the rear of the unit. To do so:a.- Re

Page 127

and secure it by inserting the 4 fastening pins into the corresponding slots, Figure 148: Insert the fastening pins into the corresponding slots.212C

Page 128

7.2.- RELAY DIGITAL INPUTS/OUTPUTS This expansion module features 8 relay digital inputs and 8 relay digital outputs.7.2.1.- CONNECTION TERM

Page 129

7.2.2.- CONNECTION DIAGRAMSA.- Relay digital outputs1 2 3 4 5 6 7 8 9 10RelayExternal powerFigure 151: Connection diagram, relay digital outputs.B.- D

Page 130

7.2.3.- CONFIGURATIONYou can access the setup menu on the main screen, Figure 25.The screen in Figure 153, is the home screen of the setup menu.Figure

Page 131

Displayed here are all the expansion modules connected to the unit. If in the unit there is more than one module of the same type connected, a number

Page 132

7.2.3.1.- Digital inputs.The operating mode for 8 digital inputs and the parameters for each mode are selected in the main conguration screen for

Page 133 - Figure 120

7.2.3.1.1.- Conguration of a digital input, impulse mode.When selecting the conguration of digital inputs in impulse mode, you can program the f

Page 134

... Digital outputs of 1 to 8, to select the conguration of each of the 8 relay digital outputs. Back, returns to the main screen for relay d

Page 135

3.5.- STARTING UP THE UNITOnce the CVM-B is connected to the power supply, the following screen, Figure 11, appears on the display and checks th

Page 136

7.2.4.1.- Programming of relay digital outputsThe following functions are implemented for these variables: Function 0x04: reading registers. Function

Page 137 - Figure 123:

Table 70: Modbus memory map: Relay digital outputs, expansion modules (Table 3).Conguration of the relay digital outputs : Slot 2Configuration variab

Page 138

Table 72:Modbus memory map: Relay digital outputs, expansion modules (Table 5).Conguration of relay digital outputs: Slot 4Configuration variableAddr

Page 139

Table 75: Modbus memory map: Manual programming of outputs, expansion modules (Table 3).Manual programming of relay digital outputs: Slot 2 Configurat

Page 140 - Figure 125:

7.2.4.5.- Status of relay digital outputsThe following functions are implemented for these variables: Function 0x04: reading registers. Function 0x10:

Page 141 - Figure 126: The C0

Table 79: Modbus memory map: Status of relay digital outputs (Table 2).Status of relay digital outputs: Slot 1Configuration variableAddress Output 1Ou

Page 142

Table 81: Modbus memory map: Status of relay digital outputs (Table 4).Status of relay digital outputs: Slot 3Configuration variableAddress Output 1Ou

Page 143 - Figure 127: The C0

7.3.- TRANSISTOR DIGITAL INPUTS/OUTPUTSThis expansion module contains 8 transistor digital inputs and 8 transistor digital outputs.7.3.1.- CONN

Page 144 - Figure 113

7.3.2.- CONNECTION DIAGRAMSA.- Transistor digital outputs1 2 3 4 5 6 7 8 9 10OptocouplerExternal power+-Figure 160:Connection diagram, transistor digi

Page 145

7.3.3.- CONFIGURATIONYou can access the setup menu on the main screen, Figure 25.The screen in Figure 162, is the home screen of the setup menu.Figure

Page 146 - L1 L2 L3 III

If this is the rst time the unit is switched on, the screen in Figure 13 appears to select the language.Figure 13: Language selection screen.The foll

Page 147

Displayed here are all the expansion modules connected to the unit. If in the unit there is more than one module of the same type connected, a number

Page 148

7.3.3.1.- Digital inputs.The conguration of the digital inputs is the same as the conguration of the digital inputs in the relay digital inputs/o

Page 149

7.3.4.- COMUNICACIONES MODBUSThe address of the Modbus memory map depends on the position of the expansion module in the unit.Slot 1 will be the posit

Page 150

Table 86: Modbus memory map: Transistor digital outputs, expansion modules (Table 2).Transistor Digital Outputs conguration: Slot 1Configuration vari

Page 151

Table 88: Modbus memory map: Transistor digital outputs, expansion modules (Table 4).Transistor Digital Outputs conguration: Slot 3Configuration vari

Page 152

7.3.4.2.- Manual programming of transistor digital outputsThe following functions are implemented for these variables: Function 0x04:reading registers

Page 153

Table 94: Modbus memory map: Manual programming of outputs, expansion modules (Table 5).Manual programming of transistor digital outputs: Slot 4 Confi

Page 154

Table 97:Modbus memory map: Digital inputs, expansion modules (Table 3).Conguration of digital inputs: Slot 2 Configuration variableAddress Input 1 I

Page 155

7.3.4.4.- Status of digital inputsThe following functions are implemented for these variables: Function 0x04: reading registers.Table 100: Modbus memo

Page 156

Table 103: Modbus memory map: Status of digital inputs (Table 4).Status of digital inputs: Slot 4Configuration variable Address Valid data windowInpu

Page 157

The digit selected is indicated in white.The following options appear in the lower area: , ... the ten possible digits to program. Previous, sel

Page 158

Table 105: Modbus memory map: Status of transistor digital outputs (Table 2).Transistor digital outputs: Slot1Configuration variableAddress AlarmImpul

Page 159

Table 106 ( Continuation): Modbus memory map: Status of transistor digital outputs (Table 3).Estado de las Salidas Digitales de Transistor : Slot 2Var

Page 160

Table 108: Modbus memory map: Status of transistor digital outputs (Table 5).Transistor digital outputs: Slot4Configuration variableAddress AlarmImpul

Page 161 - Figure 133

7.4.- ANALOGUE INPUTS/OUTPUTSThis expansion module contains 8 analogue outputs and 4 analogue inputs.7.4.1.- CONNECTION TERMINALSA.- Terminals

Page 162

B.- Terminals on the lower faceTable 110: List of terminals on the lower face, Analogue inputs/outputs module.Unit terminals10: I1+, Analogue input 1

Page 163

7.4.2.- CONNECTION DIAGRAMSA.- Analogue outputs19External loadDADAFigure 168:Connection diagram, analogue outputs.B.- Analogue inputs1017DADASensor0/4

Page 164

7.4.3.- CONFIGURATIONYou can access the setup menu on the main screen, Figure 25.The screen in Figure 170, is the home screen of the setup menu.Figure

Page 165

Displayed here are all the expansion modules connected to the unit.If in the unit there is more than one module of the same type connected, a number w

Page 166

7.4.3.1.- Analogue inputs.Select the input to congure on the main conguration screen for the analogue inputs, Figure 173.Figure 173: Main congur

Page 167 - Figure 137

Figure 174: Analogue inputs conguration screen.The parameter selected is indicated in white.The following options appear in the lower area:● When pr

Page 168

Next, selects the next parameter.Use the keys and to select the different options; once selected, conrm by choosing the option and pressing t

Page 169

Conrm, conrms and saves in the memory the values programmed on the screen. Back, returns to the main conguration screen for analogue inputs,

Page 170

Next, selects the next parameter. Conrm, conrms and saves in the memory the values programmed on the screen. Back, returns to the main con

Page 171

If no key is pressed for 5 minutes, the display screen changes automatically to the default screen, which displays the voltage measurement of 4 parame

Page 172

● When programming the scale: 0... 20mA, to select the scale from 0 to 20mA. 4... 20mA, to select the scale from 4 to 20mA. 0... 10V, to select

Page 173

7.4.4.- MODBUS COMMUNICATIONSThe address of the Modbus memory map depends on the position of the expansion module in the unit.Slot 1 will be the posit

Page 174

Table 113: Modbus memory map: Analogue outputs, expansion modules (Table 3).Conguration of analogue outputs: Slot 2Configuration variableAddress Outp

Page 175

7.4.4.2.- Programming analogue inputsThe following functions are implemented for these variables: Function 0x04: reading registers. Function 0x10:Wri

Page 176

Table 119: Modbus memory map: Analogue inputs, expansion modules (Table 4).Conguration of analogue inputs: Slot 3Configuration variableAddress Input

Page 177 - Table 23

Table 123: Modbus memory map: Analogue inputs, expansion modules (Table 8).Status of the analogue inputs: Slot 3Configuration variable Address Valid

Page 178

7.5.- MODBUS/TCP BRIDGE COMMUNICATIONS MODULEThe M-CVM-AB-Modbus TCP ( Bridge) is a communications module for connecting the CVM-B units to a M

Page 179

4.- OPERATION 4.1.- OPERATING PRINCIPLEThe CVM-B is a four-quadrant power analyzer (consumption and generation).0º90º180º-90ºCapacitiveCapacit

Page 180

7.5.3.- CONNECTION DIAGRAMB(-)A(+)SPCEthernetRS-485POWER SUPPLYINPUTSA(+) B(-)GNDRS485S1 S2S1 S2S1 S2L1P1 P2L2L3300V ~Ph-NPh-Ph520V ~NVL3L2VL1VP1 P2P1

Page 181

All the possible programming parameters for the unit appear in the lower area. To congure the expansion modules you need to, using the keys and , b

Page 182

Figure 182: Main conguration screen of the Modbus TCP communications module.The following options appear in the lower area: Conguration of DHCP act

Page 183

7.5.4.1.- Conguration of DHCP activation/deactivationOn this screen you select whether or not the IP is automatically assigned. Figure 183.Figure

Page 184

7.5.4.2.- Conguration of the TCP parameters manually.Note: If DHCP is activated, you will not be able to modify the parameters on this screen. This

Page 185

7.5.4.3.- Conguration of the RS-485 gateway parametersThe conguration parameters of the RS-485 gateway are, Figure 185:  The transmission spee

Page 186

● When programming the parity: Even parity. Odd parity. No parity. Previous, selects the previous parameter. Next, selects the next param

Page 187

7.5.5.- MODBUS COMMUNICATIONSThe following functions are implemented for these variables: Function 0x04: reading registers. Function 0x10: Writing mul

Page 188

7.6.- LONWORKS COMMUNICATIONS MODULE The LonWorks communications module, M-CVM-AB-LON, enables communicating the CVM-B on a LonWorks networ

Page 189

7.6.3.- CONFIGURATIONYou can access the setup menu on the main screen, Figure 25.The screen in Figure 188, is the home screen of the setup menu.Figure

Page 190

4.2.- MEASUREMENT PARAMETERSThe unit displays the electrical parameters shown in Table 5.Table 5: CVM-Bx measurement parameters.Parameter Units

Page 191

Displayed here are all the expansion modules connected to the unit.If in the unit there is more than one module of the same type connected, a number w

Page 192

Figure 191: Main conguration screen of the LonWorks module ( Message)The following options also appear at the bottom: Conrm, for deleting the messa

Page 193

7.6.5.- LIST OF LONWORKS LOGSNote: The binary les and setup le can be downloaded from Circutor’s website.Variable Name Variable type UnitCurrent L1n

Page 194

Variable Name Variable type UnitActive power L2nvo_ActPwrPh2 SNVT_power_kilo (28) kW L2Code Resolution Values08 0.1 0..6553.5Active power L3Name Varia

Page 195

Variable Name Variable type UnitCurrent THD L2nvo_THDVal_I2 SNVT_lev_percent (81) THD A% L2Code Resolution Values29 0.005 -163.840..163.830Current THD

Page 196 - Table 50:

Variable Name Variable type UnitThree-phase CurrentnvoAvgValCurr3Ph SNVT_amp_ac (139) I_AVGCode Resolution Values31 1 0..65,534Current Maximum Demand

Page 197

Variable Name Variable type UnitInductive Reactive Energy (-)nvoIndEnergy_exp SNVT_elec_kwh_I (146) kVArL.h(-)Code Resolution Values48 0.1 -214,748,36

Page 198

Arrray 1 tipo NVT ( SNVT_str_int (37)), Unit (N/A), Resolution (1), Values (0...65,565), Bytes (31)

Page 199

Arrray 3 tipo NVT ( SNVT_str_int (37)), Unit (N/A), Resolution (1), Values (0...65,565), Bytes (31)

Page 200

Arrray 3 tipo NVT ( SNVT_str_int (37)), Unit (N/A), Resolution (1), Values (0...65,565), Bytes (31)

Page 201

Table 5 ( Continuation ): CVM-Bx measurement parameters.Parameter UnitsPhases L1-L2-L3NTotalIIIMaximum Apparent Power Demand, Tariff 1 kVA Maximum C

Page 202

7.7.- PROFIBUS COMMUNICATIONS MODULEThe Probus communications module, M-CVM-AB-Probus, enables communicating the CVM-B with a Probus

Page 203

7.7.3.- CONNECTION DIAGRAMRed Profibus / Network ProfibusMaster ProfibusCVM-B1xx+ M-CVM-AB-ProbusCVM-B1xx+ M-CVM-AB-ProbusFigure 194:Connection diag

Page 204

7.7.4.- CONFIGURATIONYou can access the setup menu on the main screen, Figure 25.The screen in Figure 195, is the home screen of the setup menu.Figure

Page 205 - “6.5.- PICS MAP”)

Displayed here are all the expansion modules connected to the unit. If in the unit there is more than one module of the same type connected, a number

Page 206 - 6.5.- PICS MAP

7.7.5.- MODBUS COMMUNICATIONSThe following functions are implemented for this variable: Function 0x04: reading logs. Function 0x10: Writing multiple l

Page 207

Table 138: GSD modules (Module 1 - Mod 1.2)Mod 1.2Phase currents Symbol Bytes Address UnitsCurrent A 1 4 02-03 mACurrent A 2 4 12-13 mACurrent A 3 4 2

Page 208

Module 3Table 143: GSD modules (Module 3 - Mod 3.1)Mod 3.1Average values Symbol Bytes Address UnitsAverage phase voltage Vn_AVG 4 3C-3D Vx100Average l

Page 209

Module 5Table 147: GSD modules (Module 5)Mod 5THD V / I Symbol Bytes Address UnitsV 1 THD ratio THDV1 4 4E-4F %x100V 2 THD ratio THDV2 4 50-51 %x100V

Page 210 - Figure 144

Table 148 ( Continuation) : GSD modules (Module 8)Mod 8Odd harmonics voltage Symbol Bytes Address Units7th Order Harmonic vn H7 2 0AC8 %x1009th Order

Page 211 - Protective cover

Table 149 ( Continuation) : GSD modules (Module 9)Mod 9Odd harmonics current Symbol Bytes Address UnitsIn 9th Order Harmonic in H9 2 0BF6 %x100In 11th

Page 212

4.4.- DISPLAYThe unit has a colour TFT display which displays all the parameters indicated in Table 5.The display is divided into three areas (

Page 213

7.8.- MBUS COMMUNICATIONS MODULEThe MBus communications module, M-CVM-AB-MBus, enables communicating the CVM-B with a M-Bus network.7.8.1.- CON

Page 214 - External power

7.8.3.- CONFIGURATIONYou can access the setup menu on the main screen, Figure 25.The screen in Figure 200, is the home screen of the setup menu.Figure

Page 215 - Figure 154

Displayed here are all the expansion modules connected to the unit. If in the unit there is more than one module of the same type connected, a number

Page 216 - Figure 155

Maximum value: 250.Minimum value: 1.Use the and buttons to select the different options.To conrm the selection, press the button.If no button i

Page 217

7.8.5.- M-BUS COMMUNICATIONSThe M-Bus module implements a slave M-Bus interface that is compatible with the EN13757-2 and EN13757-3 standards, enablin

Page 218

7.8.5.1.- TABLE OF “RSP_UD” TELEGRAM VARIABLESVariables arranged by order of appearance in the telegram.Table 153: Table of “RSP_UD” telegram variable

Page 219

7.9.- DATA STORAGE MODULE, DATALOGGERThe M-CVM-AB-Datalogger can be used to store data in the embedded PowerStudio platform integrated in the m

Page 220

7.9.3.- CONNECTION DIAGRAMPCEthernetROUTERSERVIDOR/ SERVERINTERNETCon navegador Web compatible con JavaOpcional / Optional CVM B-1xx+M-CVM-AB-Datalog

Page 221

7.9.4.- CONFIGURATIONYou can access the setup menu on the main screen, Figure 25.The screen in Figure 206, is the home screen of the setup menu.Figure

Page 222

Displayed here are all the expansion modules connected to the unit. If in the unit there is more than one module of the same type connected, a number

Page 223

SAFETY PRECAUTIONS DISCLAIMERCIRCUTOR, SA reserves the right to make modi cations to the device or the unit speci ca-tions set out in this instruct

Page 224

 Type of communications The CVM-B units have one RS-485 communications port. The unit has as standard two communications protocols: MODBUS RTU ®

Page 225

7.9.4.1.- Conguration of the TCP parametersThis screen displays the conguration of the TCP parameters Figure 209, since these values cannot be co

Page 226

Figure 210:Port conguration screen.The following options appear in the lower area: Back, returns to the main conguration screen of the Datalogger

Page 227

8.- SOFTWARE UPDATEIn the CVM-B you can update:  The unit software,  The expansion modules software.Before carrying out any updating process, t

Page 228 - Optocoupler

8.1.- UNIT SOFTWARE UPDATE.The update les depend on the model of the unit:Table 158:Display software update les.Model Display software update

Page 229 - Figure 163

The updated information on the modules is displayed in the expansion modules section of the information menu, “5.5.3.- Expansion modules.” Figure 2

Page 230 - Figure 164

9.- TECHNICAL FEATURESAC power supplyRated voltage 85 ... 265 V ~Frequency 50 ... 60HzConsumptionCVM-B100 CVM-B1506... 8 VA 7...12 VAInstallation ca

Page 231

(Continuation) Accuracy of measurements (in accordance with the IEC 61557-12 standard for PMD SD/SS) .../5A .../1A .../0.250AActive energy measurement

Page 232

User interfaceDisplay: Type TFT colour screenDisplay: Resolution VGA (640x480)Display: Format 4:3Display: Visible area sizeCVM-B100 CVM-B1503.5” 5.6”K

Page 233

1441447 38968.2589.5137.6Figure 214:CVM-B150 dimensions.StandardsSafety requirements for electrical equipment for measurement, control and laboratory

Page 234

10.- TECHNICAL FEATURES OF EXPANSION MODULES 10.1.- TRANSISTOR DIGITAL INPUTS/OUTPUTS General featuresMaximum power of the module 3 WTransistor

Page 235

4.4.2.- LOWER AREAFigure 21: Lower area of display.The various options on the display and setup menus and an explanatory text for the option se-lected

Page 236

10.2.- RELAY DIGITAL INPUTS/OUTPUTS General featuresMaximum power of the module 3 WRelay digital outputsQuantity 8Maximum voltage, open contact

Page 237

10.3.- DIGITAL ANALOGUE INPUTS/OUTPUTS General featuresMaximum power of the module 3WAnalogue outputsQuantity 8Maximum internal voltage 12 VLin

Page 238

10.4.- MODBUS TCP ( Bridge ) COMMUNICATIONS General featuresMaximum power of the module 2 WCommunications : Modbus TCPConnector RJ-45Protocol M

Page 239

10.5.- LONWORKS COMMUNICATIONS General featuresMaximum power of the module 1.2 WCommunications Protocol LonTalkEnvironmental featuresOperating

Page 240

10.6.- PROFIBUS COMMUNICATIONS General featuresMaximum power of the module 2 WCommunicationsConnector DB9Protocol ProbusIdentier 4Baud rate

Page 241

10.7.- MBUS COMMUNICATIONS General featuresMaximum power of the module 2 WCommunications Bus Wired M-BusProtocol Slave M-Bus compatible to EN

Page 242

10.8.- DATA STORAGE, DATALOGGER General featuresMaximum power of the module 2 WCommunications : Modbus TCPConnector RJ-45Protocol Modbus/TCPBa

Page 243

89.589.521.8528.65Figure 216: Expansion module dimensions ( Protective cove version 2).317Instruction ManualCVM-B100 - CVM-B150

Page 244

11.- MAINTENANCE AND TECHNICAL SERVICE 12.- GUARANTEE• No returns will be accepted and no unit will be repaired or replaced if it is not ac-companied

Page 245 - 150Ω 150Ω

13.- CE CERTIFICATE319Instruction ManualCVM-B100 - CVM-B150

Page 246 - Figure 171

If an alarm has not been programmed for the parameter, the pre-alarm and alarm zones shown in the bar chart are calculated.Figure 23: Calculation of t

Page 247 - Figure 172

CIRCUTOR, SA Vial Sant Jordi, s/n08232 -Viladecavalls (Barcelona)Tel.: (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14 www.circutor.es central@circuto

Page 248

 Frequency 60 Hz L = 55 H = 65 Min = L * 0.95

Page 249

4.5.- LED INDICATORSThe CVM-B unit features: - A CPU LED, which indicates that the unit is working correctly with a 1 second ashing. A ashing

Page 250

4.6.- INPUTS The CVM-B has two programmable digital inputs (terminals 7 and 8 in Figure 1) for working as:  Logic input.  Impulse input. 

Page 251

5.- DISPLAY AND CONFIGURATIONOn the main screen, Figure 25, you can access the various menus of the unit:Figure 25:Main screen. Measurement display m

Page 252

5.1.-MEASUREMENT DISPLAY MENU The screen in Figure 26 is the home screen for the measurement display menu.Figure 26: Main screen of the measure

Page 253

5.1.1.- Display 1 parameter. By selecting this option, you want to view a single parameter on the display.Figure 27: 1 parameter display screen.The

Page 254

5.1.1.1.- Default parameters.This menu allows you to view the following types of parameters:Figure 28:Default parameters display screen (display 1 p

Page 255

CONTENTSSAFETY PRECAUTIONS ...

Page 256

5.1.1.1.1.- Instantaneous parameters.On this screen, Figure 29, you can view all the parameters indicated in Tabla 8.Figure 29: Instantaneous parame

Page 257

Table 8 ( Continuation) : Instantaneous parameters.IconDisplay 1 parameterInstantaneous parametersTotal reactive power (1)Apparent power (1)Power fact

Page 258

Figure 30: Instantaneous parameters without lower area (display 1 parameter).Press the key to display the lower area again.The following icons also

Page 259

Graphic view. (“5.1.1.1.1.1.1.Graphic view.”) Analog view. ( “5.1.1.1.1.1.2. Analog view.”) Display of 3 parameters, moves to the 3 parameters di

Page 260

5.1.1.1.1.1.2.- Analog view.The analogue display screen is shown in Figure 33.Figure 33:Instantaneous parameters, analog view(display 1 parameter).

Page 261 - Figure 182

5.1.1.1.2.- Incremental parameters.On this screen, Figure 34, you can view all the parameters indicated in Tabla 9.For each of the incremental param

Page 262

Figure 35: Graphical representation of the energy increase.NB: This representation is not real, it is only signicant to give the user an idea of the

Page 263

5.1.1.1.2.1.- Incremental parameters display menu.For each incremental parameter, this menu enables the following (Figure 36):Figure 36: Incremental p

Page 264

5.1.1.1.2.1.1.- Tariff selection.The screen for selecting the tariff to be displayed is shown in Figure 37.Figure 37:Incremental parameters, tariff

Page 265

5.1.1.1.2.1.2.- Graphic viewThe graphical representation of the energy closes is shown for all the incremental energy parameters, Figure 38.Figure

Page 266

5.5.1.- System information. ... 1115.5.2.-

Page 267

5.1.1.1.3.- Demand parameters.On this screen, Figure 39, you can view all the maximum demand parameters indicated in Tabla 10.For each of the deman

Page 268

The associated output in the module.The alarm status: not activated, pre-alarm activated, alarm activated.The icon flashes during the dela

Page 269 - Figure 189

5.1.1.1.3.1.1.- Graphic view.Figure 41 shows the graphical display screen.Figure 41:Demand parameters, graphic view (displays 1 parameter).The menu

Page 270 - Figure 191

5.1.1.1.3.1.2.- Analogue view.The analogue display screen is shown in Figure 42.Figure 42:Demand parameters, analog view (display 1 parameter).The m

Page 271

5.1.1.1.3.1.3.- Tariff selection.The screen for selecting the tariff to be displayed is shown in Figure 43.Figure 43: Demand parameters, tariff sel

Page 272 - 7.6.5.- LIST OF LONWORKS LOGS

5.1.1.2.- Customise parametersOn this screen, Figure 44, you can view the ve custom screens with 1 parameter.Figure 44: Custom parameters screen (d

Page 273

5.1.1.2.1.- , ... Customisation screensFigure 45 shows the screen used to customise 1 parameter.These screens can also be congured for communic

Page 274

5.1.1.2.1.1.- Parameter selectionFigure 46 shows the screen for selecting the parameter for display.Figure 46: Custom parameters screen, parameter s

Page 275

5.1.1.2.1.1.1.- Selecting an instantaneous parameter.Figure 47 shows the screen for selecting the Instantaneous parameters.Figure 47: Custom paramet

Page 276

To select a parameter, press the button to open the menu at the bottom for selecting the phase:● For the Neutral-Phase and Voltage parameters: Pha

Page 277

7.2.4.- MODBUS COMMUNICATIONS ... 2197.3.- TRANSISTO

Page 278

5.1.1.2.1.1.2.- Selecting an incremental parameter.Figure 48 shows the screen for selecting an incremental parameter.Figure 48: Custom parameters sc

Page 279

● For the Active tariff time, CO2 Emissions and Cost parameters: Phase L1.The tariff must be selected after selecting the phase: Tariff 1, T

Page 280

Press the key to display the lower area again.The menu at the bottom displays all the available demand parameters (Table 13).Table 13: Demand parame

Page 281 - 7.7.3.- CONNECTION DIAGRAM

5.1.2.- Display 3 parameters.By selecting this option, you can view the three parameters at the same time on the display.Figure 50: 3 parameter disp

Page 282 - Figure 196

5.1.2.1.- Default parameters.This menu allows you to view the following types of parameters:Figure 51:Default parameters display screen (display 3 p

Page 283

5.1.2.1.1.- Instantaneous parameters.On this screen, Figure 52, you can view all the parameters indicated in Table 14.Figure 52: Instantaneous param

Page 284 - Figure 136

Table 14 ( Continuation) : Instantaneous parameters (display 3 parameters).IconDisplay 3 parametersInstantaneous parametersCapacitive reactive power L

Page 285 - Module 2

5.1.2.1.1.1.- Instantaneous parameters display menu.For each instantaneous parameter, this menu allows (Figure 53):Figure 53: Instantaneous parameters

Page 286 - Module 4

The menu in the lower area disappears after 3 seconds.Press the key to display the lower area again.The lower area menu options are: , , Selectin

Page 287 - Module 8

Table 15: Instantaneous parameters (display 3 parameters).IconDisplay 3 parametersIncremental parametersActive energy L1(1) (2)Active energy L2 (1) (2

Page 288 - Module 9

REVISION LOGTable 1: Revision log.Date Revision Description06/14 M010B01-03-14A Initial Version05/15 M010B01-03-15AIntroduction of expansion modules:

Page 289 - Module 13

5.1.2.1.2.1.- Incremental parameters display menu.For each incremental parameter, this menu enables the following (Figure 56):Figure 56: Incremental p

Page 290

5.1.2.1.2.1.1.- Tariff selection.The screen for selecting the tariff to be displayed is shown in Figure 57.Figure 57:Incremental parameters, tariff

Page 291 - Figure 201

5.1.2.1.2.1.2.- Graphic view.The graphical representation of the energy closes is shown for all the incremental energy parameters, Figure 58.Figure

Page 292

5.1.2.1.3.- Demand parameters.On this screen, Figure 59, you can view all the maximum demand parameters indicated in Table 16.For each of the dema

Page 293

The following icons also appear in the active power maximum demand parameters: Indicating that the parameter refers to inductive or capacitive energ

Page 294

Graphic view .(“5.1.2.1.3.1.1. Graphic view”) Tariff selection (“5.1.2.1.3.1.2. Tariff selection.”) Back, returns to the demand parameters disp

Page 295

5.1.2.1.3.1.2.- Tariff selection.The screen for selecting the tariff to be displayed is shown in Figure 62.Figure 62:Demand parameters, tariff selec

Page 296

5.1.2.2.- Customise parameters On this screen, Figure 63, you can view the ve custom screens with 3 parameters.Figure 63: Custom parameters screen

Page 297 - 7.9.3.- CONNECTION DIAGRAM

5.1.2.2.1.- , ... Customisation screensFigure 64 shows the screen used to customise 3 parameters.These screens can also be configured for c

Page 298 - Figure 207

5.1.3.- Display 4 parameters.By selecting this option, you can view the four parameters at the same time on the display.Figure 65: 4 parameter displ

Page 299

1.- VERIFICATION UPON RECEPTIONCheck the following points upon receiving the unit: a) The unit meets the specications described in your order. b)

Page 300

5.1.3.1.- Default parameters.This menu allows you to view the following types of parameters:Figure 66:Default parameters display screen (display 4 p

Page 301 - Figure 208

5.1.3.1.1.- Instantaneous parameters.On this screen, Figure 67, you can view all the parameters indicated in Table 17.Figure 67: Instantaneous param

Page 302

Table 17 ( Continuation) :Instantaneous parameters (display 4 parameters).IconDisplay 4 parametersInstantaneous parametersActive power L1 (2)Active po

Page 303

If there is an alarm associated with the variable being displayed, the following will be shown: The module with which the alarm is associated. The as

Page 304

5.1.3.1.1.1.1.- Graphic view.Figure 69 shows the graphical display screen .Figure 69: Instantaneous parameters, graphical representation (displays 4

Page 305 - 9.- TECHNICAL FEATURES

5.1.3.1.2.- Incremental parameters.On this screen, Figure 70, you can view all the parameters indicated in Table 18.For each of the incremental para

Page 306

Table 18 ( Continuation): Incremental parameters (display 4 parameters).IconDisplay 4 parametersIncremental parametersActive tariff hoursActive tariff

Page 307

5.1.3.1.2.1.- Incremental parameters display menu.For each incremental parameter, this menu enables the following (Figure 71):Figure 71: Incremental p

Page 308

5.1.3.1.2.1.1.- Tariff selection.The screen for selecting the tariff to be displayed is shown in Figure 72.Figure 72:Incremental parameters, tariff

Page 309

5.1.3.1.2.1.2.- Graphic view.The graphical representation of the energy closes is shown for all the incremental energy parameters, Figure 73.Figure

Page 310

- 2 digital inputs, to select the tariff, detect the logic state of external signals or as act as an impulse input. - 2 transistor digital outpu

Page 311

5.1.3.1.3.- Demand parameters.On this screen, Figure 74, you can view all the maximum demand parameters indicated in Table 19.For each of the demand

Page 312

Use the keys and to browse the various parameters.If there is an alarm associated with the variable being displayed, the following will be shown:

Page 313

Back, returns to the demand parameters display screen, Figure 74. Main Menu, back to the main menu, Figure 25.Use the keys and to browse the d

Page 314

5.1.3.1.3.1.2.- Tariff selection.The screen for selecting the tariff to be displayed is shown in Figure 77.Figure 77:Demand parameters, tariff sele

Page 315 - 10.7.- MBUS COMMUNICATIONS

5.1.3.2.- Customise parameters On this screen, Figure 78, you can view the ve custom screens with 4 parameters.Figure 78: Custom parameters screen

Page 316

5.1.3.2.1.- , ... Customisation screensFigure 79 shows the screen used to customise 4 parameters.These screens can also be configured for c

Page 317

5.1.4.- Phasors.By selecting this option, you can view the phase sequence ( Figure 80).Figure 80: Phasor display screen.The following options appear

Page 318

5.1.5.- Standard phasors.By selecting this option, you can view the phase sequence with the standard values ( Figure 81).Figure 81: Standardised ph

Page 319 - 13.- CE CERTIFICATE

5.1.6.- Harmonics.On this screen, Figure 82, you can view the harmonics of the parameters indicated in Table 20.Figure 82: Harmonics screen.Table 20

Page 320 - Vial Sant Jordi, s/n

, Select the display of the even or odd harmonics . Previous, you move through the harmonics in descending order. Next, you move through th