Circutor CVM-B Series Manuel d'utilisateur Page 33

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 320
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 32
Frequency 60 Hz
L = 55 H = 65
Min = L * 0.95 Max = H * 1.05
PL = L + (( H - L) * 0.25) PH = H - (( H - L) * 0.25)
Voltage THD
L = 0 H = 5
Min =0 Max = H * 2
PL = L + (( H - L) * 0.25) PH = H - (( H - L) * 0.25)
The alarm and pre-alarm zones L are not displayed.
Current THD
L = 0 H = 20
Min =0 Max = H * 2
PL = L + (( H - L) * 0.25) PH = H - (( H - L) * 0.25)
The alarm and pre-alarm zones L are not displayed.
Cosine phi and Power factor
L = -0.9 H = 0.9
Min = -Max Max = minor(L or H) * 1.2
PL = L + (( L - H+2) * 0.25) PH = H + (( L - H+2) * 0.25)
33
Instruction Manual
CVM-B100 - CVM-B150