CONFIGURATION
4.7.1.2. Digital outputs conguration
On this screen, equations are congured for the alarms that are applied to activate the system
outputs. Equations can be congured using AND (*) and/or OR (+) functions between one or
more of the 16 previously congured alarms (see Section 4.7.1.1., Alarm Conguration), in
order to activate each one of the card's 8 digital outputs.
To modify the card equations' conguration parameters, press the EDIT button (F4). Select the
output to be congured and press SET to begin editing.
4.7.1.1.b Reverse conguration logic output
When a variable code corresponding to the status of an expansion card input is selected, an
alarm can be activated in one of two possible ways: direct or inverse logic.
To congure the alarms using direct logic, with respect to the input, [i.e., the alarm activates
(value = 1) when the input activates (value = 1)], the parameters should be congured as
follows:
max = 1 and min = -1.
To congure the alarms using inverse logic, with respect to the input, [i.e., the alarm activates
(value = 0) when the input deactivates (value = 1)], the parameters should be congured as
follows:
max = 0 and min = 0.
Edit the two digits in the equation that correspond to the appropriate alarm. Between the two
digits corresponding to the alarm, an "*" or "+" sign can be entered. These correspond to the
AND or OR functions, respectively, and will be applied between the alarms congured.
Press (F3) to return to the ALARM 01 screen (Section 4.7.1.1).
Press (F1) to return to the inputs screen (Section 4.7.1.3).